Speed Control Wiring
10
CONNECTION DIAGRAM FOR 2-WIRE CONTROLS
Switch
Ground (Earth)**
Controlled
Load
TRIAC
AC
LINE
APPLICATION
• Motor Type - Shaded Pole, PSC and Universal.
• Required Load - Fans and speed dependant loads.
WIRING
• Warning! - Power must be turned off before wiring. Connect control in series with motor and line voltage - never connect
control across line.
MOUNTING
• Use 2” deep standard electrical Box.
• Secure control with outer bracket tabs.
MINIMUM SPEED ADJUSTMENT
• Motor must be in actual operating conditions to achieve proper speed adjustment. (Motor will not slow down unless
proper load is applied).
• Turn main control knob clockwise to lowest speed position.
• Locate and adjust minimum speed setting on front plate with screw driver (rotate clockwise to decrease minimum speed;
counter-clockwise to increase minimum speed.
• Note: For all high current models, 8 amps or greater, the opposite minimum speed rotation adjustment must be made so
that motor runs with sufficient torque to prevent stalling.
• Motor will now operate from this preset minimum speed to full speed.
FINAL MOUNTING
• Install front dial plate - remove protective plastic.
• Turn main control until switch snaps off.
• Push on knob so that pointer is off position.
NOTE: For no switch models install front dial plate and push on knob.
TRIAC SIZING CONSIDERATIONS
• ** Some models do not require grounding. Therefore, a ground wire is not provided.
• Make sure the total circuit amperage load does not exceed the TRIAC’s rated amperage.
• Make sure TRIAC’s voltage rating matches line voltage.
SAFETY WARNING!
Unit should be installed by a qualified electrician in
accordance with the National Electrical Code and other
local codes which may apply. This control must be
grounded when installed. Failure to follow these instruc-
tions may result in electrical shock or a fire hazard. This
control is suitable for mounting in a metal or approved
enclosure. These controls must not be used for loads
exceeding those ratings clearly marked on the device.